Test appliances and extension leads as per the AS/NZ3760 standard with the new Kyoritsu 6205 Portable Appliance Tester. Highly reliable and user-friendly. Powered by battery with built-in RCD testing function.

The new Kyoritsu 6205 pat tester has a variety of features for a more convenient pat testing. Test and tag electronic devices as per AS/NZ3760 standard. Comes with RCD 10mA/30mA testing with built in isolation transformer.

Features

  • Powered by battery
  • Store up to 999 test results
  • Printer and software compatible
  • PASS/FAIL indicators
  • Test results display on screen
  • Meets the AS/NZS 3760 Standard

 

Check out our PAT Testing Equipment Buying Guide for more info. Or contact an expert! 📞ℹ️

 

Description

The KYORITSU 6205 Portable Appliance Tester can perform test as required by the following standards – AS/NZS 3760 In-service safety inspection and testing of electrical equipment.

Power source LR6(AA)(1.5V) × 6
Applicable Standards IEC/EN61010-1 CAT II 300V, IEC/EN61010-2-030,
IEC/EN61010-031, EN61326-2-2, AS/NZ3760
Dimentions / Weight 261(L) × 104(W) × 57(D)mm / Approx. 930g(including batteries)
Included Accessories 7277(Mains lead),
7129A(Test lead with Alligator clip),
7161A(Flat test prod),
7276(Adaptor for Extension cord),
9193(Carrying case),
8928(Fuse[10A/250V]),
9121(Shoulder strap),
Buckle, LR6(AA) x 6, Instruction manual

Specifications

Function Tests of contents
Class Ⅰ Test • Protective conductor resistance
(Test current 200mA DC nominal)
• Insulation resistance test (250V or 500V)
• Leakage current test (100-253V/50Hz)
• Load current test (100-253V/50Hz)
Class Ⅱ Test • Insulation resistance test (250V or 500V)
• Leakage current test (100-253V/50Hz)
• Load current test (100-253V/50Hz)
Extension Lead Test • Protective conductor resistance
(Test current 200mA DC nominal)
• Insulation resistance test
(between Line/Neutral-Earth short, Line/Neutral)
• Leakage current test (100-253V/50Hz)
• Polarity test
RCD Test • RCD test (10mA/30mA)

Mains voltage indlcation

Display range 30V-270V
Accuracy ±5V

Protective conductor resistance test

Measuring range 0.00-20.00Ω
Open circuit voltage 5V±0.4V DC
Measuring current 200mA DC(nominal value)
Accuracy ±3%rdg±5dgt

Insulation resistance test

Rated volatge 250V 500V
Measuring range 0.00-20.00MΩ
No-load voltage 250V DC +20%,-0% 500V DC +20%,-0%
Short circuit current 1.5mA DC or less
Accuracy ±2%rdg±3dgt

Load current/Leakage current test

Item Load current Leakage current
Mains voltage range 100-253V/50Hz
Measuring range 0.10-10.00A rms 0.10-20.00mA rms
Accuracy ±10%rdg±5dgt ±3%rdg±5dgt

RCD test

Rated voltage 230V -15% – +10%/50Hz
Rated current 10mA/30mA
Function × 1 × 5
Test duration 0.0ms-500.0ms 0.0ms-40.0ms
Operating time accuracy ±2ms(≦40ms),±8ms(>40ms)